RCBO / RCCB installation #
MX7 has integrated RDC-DD, protecting against hazardous DC residual currents over 6mA. Installation of a Type A double-pole RCBO or RCD with 30mA earth leakage protection is required to ensure complete protection from both DC and AC residual current as well as the overcurrent and short-circuit.

Connect the power cable #
Feed the power cable through the rubber sealing located at the bottom left of the unit. Strip each wire to expose 12mm of copper, and use provided ferrules for stranded wires to ensure a secure connection. Open the terminal block slots by lifting the levers, insert the wires as marked (L, N, PE), then lower and firmly press the levers to secure the cables in place.
The charger is equipped with PEN fault protection and an automatic disconnection system, compliant with BS 7671:2018 Amendment 2:2022 (clause 722.411.4.1, 18th Edition IET Wiring Regulations).